How to calculate flow rate of cooling tower?

Published in Cooling Tower Calculation 5 mins read

To calculate the flow rate of a cooling tower, you primarily use the heat load it needs to dissipate and the desired temperature difference of the water. The most common way to determine the design flow rate (in Gallons Per Minute or GPM) involves the heat load formula.

The flow rate of a cooling tower can be calculated using the following formula, which is derived from the Cooling Tower Heat Load Calculation:

Flow Rate (GPM) = Heat Load (BTU/Hr) / (500 × ° Range of Cooling)

Let's break down this formula and understand each component.


Understanding the Cooling Tower Flow Rate Calculation

The formula provides a direct method to determine the required water flow rate based on the heat rejected by the system.

Key Components of the Formula:

  • Flow Rate (GPM): This is the volume of water flowing through the cooling tower, typically measured in Gallons Per Minute. It represents how much water needs to be circulated to achieve the desired cooling effect.
  • Heat Load (BTU/Hr): This is the total amount of heat that must be removed from the water by the cooling tower, expressed in British Thermal Units per Hour. It's the heat absorbed by the cooling water from the process or equipment it's cooling.
  • 500: This is a constant value derived from the properties of water. It accounts for the density of water (approximately 8.33 lbs/gallon), its specific heat (1 BTU/lb/°F), and the conversion from hours to minutes (60 minutes/hour). Specifically, 8.33 lbs/gallon 1 BTU/lb/°F 60 minutes/hour ≈ 500 BTU/gallon/hour/°F.
  • ° Range of Cooling: Also known as the "Delta T" or "temperature range," this is the difference between the hot water temperature entering the cooling tower and the cold water temperature leaving it. It's usually expressed in degrees Fahrenheit (°F).

Formula Breakdown Table:

Variable Unit Description
Flow Rate (GPM) GPM The volume of water circulated through the cooling tower per minute.
Heat Load BTU/Hr The amount of heat removed from the water by the cooling tower over an hour.
500 Constant A factor representing the heat-carrying capacity of water per gallon per degree Fahrenheit per hour.
° Range °F (Delta T) The temperature difference between the water entering the tower (hot) and leaving the tower (cold).

Steps to Calculate Cooling Tower Flow Rate

To accurately calculate the flow rate, follow these steps:

  1. Determine the System's Heat Load (BTU/Hr):

    • This is the most critical input. The heat load comes from the equipment or process being cooled (e.g., chillers, industrial processes, HVAC systems).
    • It can often be found in the specifications of the equipment connected to the cooling tower. For example, a chiller's cooling capacity often dictates the heat load.
  2. Define the Desired Range of Cooling (°F):

    • This is the temperature difference the cooling tower is designed to achieve.
    • For instance, if water enters at 95°F and needs to be cooled to 85°F, the range is 10°F.
    • The range is typically specified by the system's requirements.
  3. Apply the Flow Rate Formula:

    • Once you have the Heat Load and the ° Range, simply plug these values into the formula:
      GPM = Heat Load (BTU/Hr) / (500 × ° Range of Cooling)

Example Calculation:

Let's say you have a system with the following parameters:

  • Heat Load: 6,000,000 BTU/Hr (e.g., from a large industrial process or multiple chillers)
  • Desired Cooling Range: 15°F (water enters at 100°F and needs to exit at 85°F)

Using the formula:

GPM = 6,000,000 BTU/Hr / (500 × 15°F)
GPM = 6,000,000 / 7,500
GPM = 800

Therefore, the required design flow rate for this cooling tower would be 800 GPM.


Practical Considerations and Insights

  • Design vs. Actual Flow Rate: The calculated GPM is typically a design flow rate. Actual operating flow rates might vary slightly due to system balancing, pump performance, or specific operational needs.
  • Impact of Variables:
    • Higher Heat Load: Requires a higher GPM to dissipate more heat if the range is constant.
    • Wider Range of Cooling: Allows for a lower GPM to remove the same amount of heat, as each gallon removes more heat.
    • Smaller Range of Cooling: Requires a higher GPM to remove the same amount of heat, as each gallon removes less heat.
  • System Efficiency: Proper flow rate is crucial for efficient cooling tower operation. Too low a flow rate can lead to inadequate cooling and higher leaving water temperatures, while too high a flow rate can cause excessive pump energy consumption and potential water splash-out.
  • Water Treatment: Maintaining proper water chemistry is vital to ensure the longevity and efficiency of the cooling tower, regardless of the flow rate. Learn more about cooling tower water treatment from reputable sources like the EPA.
  • Instrumentation: Modern cooling towers often use flow meters and temperature sensors to monitor actual operating conditions and ensure they align with design specifications.

By accurately calculating and maintaining the correct flow rate, you ensure optimal performance, energy efficiency, and longevity of your cooling tower system.