TT and TN earthing are fundamental types of electrical grounding systems that define how electrical installations are connected to the earth. These systems ensure safety by providing a path for fault currents in the event of an insulation failure, preventing dangerous voltages on exposed conductive parts of equipment.
As per electrical standards, earthing system designations like TT and TN describe the relationship between the power supply's neutral point and the exposed conductive parts (frames) of electrical equipment, regarding their connection to earth. The provided reference states that "The third and fourth letters indicate the functions of neutral and protective conductors respectively." [14] While TT and TN systems are typically identified by two letters, these letters consistently denote specific connections: 'T' often signifies a direct connection to earth (Terra), and 'N' signifies a connection to the neutral conductor.
Understanding TT Earthing (Terra-Terra)
The TT earthing system is characterized by independent earthing connections for both the power supply transformer and the electrical installation. According to the reference, in a TT configuration, the "transformer neutral earthed and frame earthed." [14]
-
Key Characteristics:
- Transformer Connection: The neutral point of the supply transformer is directly connected to a dedicated earth electrode.
- Equipment Frame Connection: The exposed conductive parts (frames) of all electrical equipment in the consumer's installation are connected to their own, separate earth electrode, which is electrically independent of the supply's earth electrode.
- Fault Path: In case of a fault (e.g., live conductor touching the equipment frame), the fault current flows from the live conductor, through the equipment frame, through the consumer's earth electrode, into the ground, and back through the utility's earth electrode to the transformer neutral.
- Safety Devices: Due to the potentially higher impedance of the earth fault loop, Residual Current Devices (RCDs) are typically essential for fault protection in TT systems, as overcurrent devices (fuses, MCBs) might not operate quickly enough.
-
Practical Insights:
- Often used in rural areas where the impedance of the earth electrode may be high or where it's difficult to achieve a common earthing system.
- Offers good protection against faults between the live conductor and earth, as individual installations are well isolated.
Understanding TN Earthing (Terra-Neutral)
The TN earthing system establishes a direct metallic connection between the exposed conductive parts of electrical equipment and the neutral conductor of the power supply. The reference states that in a TN configuration, the "transformer neutral earthed, frame connected to neutral." [14]
-
Key Characteristics:
- Transformer Connection: The neutral point of the supply transformer is directly connected to earth.
- Equipment Frame Connection: All exposed conductive parts (frames) of electrical equipment are connected to the neutral conductor, which is then earthed back at the supply transformer. This means the protective conductor (PE) and the neutral conductor (N) are linked at some point.
- Fault Path: In the event of a fault, the fault current flows from the live conductor, through the equipment frame, and back to the transformer neutral via the protective conductor (PE). This creates a low-impedance metallic path for fault current.
- Safety Devices: The low impedance fault loop allows for rapid operation of overcurrent protective devices (fuses, Miniature Circuit Breakers - MCBs), which can clear faults quickly. RCDs may be used as supplementary protection.
-
TN Sub-types: TN systems are further categorized based on whether the neutral (N) and protective earthing (PE) functions are combined or separate:
- TN-C: Combined Neutral and Earth conductor (PEN).
- TN-S: Separate Neutral and Earth conductors throughout the system.
- TN-C-S: Combined PEN conductor from the supply, then splitting into separate N and PE conductors at the consumer's premises. This is often referred to as Protective Multiple Earthing (PME) or Multi-earthed Neutral (MEN) system.
-
Practical Insights:
- Widely used in modern residential, commercial, and industrial installations due to its low impedance fault path and effective fault clearance.
- Requires careful design to prevent breaks in the PEN conductor, which could lead to dangerous voltages on equipment frames.
Key Differences: TT vs. TN Earthing
Understanding the core distinctions between TT and TN systems is crucial for electrical design and safety.
Feature | TT Earthing | TN Earthing |
---|---|---|
Frame Connection | Independently earthed at the consumer's premises | Connected to the system neutral via a protective conductor (PE) |
Transformer Neutral | Earthed | Earthed |
Fault Path | Through the ground via separate earth electrodes | Through the protective conductor (PE) back to the transformer neutral |
Fault Loop Impedance | Generally higher | Generally lower |
Required Protection | Residual Current Devices (RCDs) are usually mandatory for primary protection | Overcurrent protective devices (MCBs, Fuses) often sufficient for primary protection, RCDs for supplementary or specific circuits |
Risk of N-PE Fault | Low, as neutral and earth are separated | Potential for neutral conductor breaks to energize frames if not properly designed (TN-C) |
Reference | "transformer neutral earthed and frame earthed." [14] | "transformer neutral earthed, frame connected to neutral." [14] |
Both TT and TN earthing systems serve the critical function of providing safety against electric shock, but they achieve this through different configurations of the protective earth conductor and its connection to the neutral point and the overall earthing system.