How to Calculate the Amps Running Through a Transformer

Published in Electrical Transformer Current 2 mins read

The number of amps running through a transformer is not a fixed value but depends on its power rating, voltage, and the load it is supplying. For control transformers, specifically, the maximum full load running amps can be precisely calculated based on its specifications.

Understanding Transformer Current

A transformer's capacity is typically rated in Volt-Amperes (VA), which represents its apparent power. This rating, along with the secondary (output) voltage, determines the maximum current it can safely deliver to a connected load.

Calculating Full Load Running Amps for a Control Transformer

To determine the proper running amps for a control transformer, you can use a straightforward calculation involving its VA rating, secondary voltage, and a de-rate factor. This calculation provides the maximum continuous current the transformer is designed to handle under full load conditions.

Here's the formula:

Maximum Full Load Running Amps = (Transformer VA Rating ÷ Secondary Voltage) × De-rate Factor

Key Components of the Calculation:

  • Transformer VA Rating: This is the apparent power capacity of the transformer, usually labeled on the unit (e.g., 40 VA, 100 VA).
  • Secondary Voltage: This is the output voltage of the transformer (e.g., 24 volts, 120 volts).
  • De-rate Factor: This factor is applied to ensure the transformer operates safely and efficiently below its theoretical maximum. A common de-rate factor used is 80% (or 0.80), accounting for various operational conditions and preventing overheating.

Example Calculation

Let's illustrate with a common example: a control transformer with a 40 VA rating and a 24-volt secondary.

Parameter Value
Transformer VA Rating 40 VA
Secondary Voltage 24 Volts
Intermediate Current (40 VA / 24 Volts) 1.67 Amps
De-rate Factor 0.80 (80%)
Maximum Full Load Running Amps 1.33 Amps

As shown, by dividing the 40 VA rating by the 24 secondary volts, you get 1.67 amps. Multiplying this by a de-rate factor of 0.80 results in 1.33 amps as the maximum full load running amps for this specific control transformer.

This calculation provides the precise current capacity, ensuring the transformer operates within its safe and efficient limits when supplying power to control circuits or other loads.