What is Honeywell Fault Code 19?

Published in Honeywell Fault Codes 4 mins read

Honeywell fault code 19 signifies a temperature fault, indicating that the gas cartridge within a device, typically a Honeywell E3Point gas detector, is experiencing temperatures outside its specified operational range. Specifically, this error is triggered when the gas cartridge temperature falls below -4 degrees Fahrenheit or rises above 122 degrees Fahrenheit.

Understanding the Temperature Fault

The E3Point and similar Honeywell devices are designed to operate accurately and safely within a specific environmental temperature window. The gas cartridge, a critical component responsible for detecting gas concentrations, relies on maintaining its temperature within this range for proper function and longevity. When its temperature deviates from -4°F to 122°F, the device issues fault code 19 to alert users to a potential issue that could compromise its performance or lead to inaccurate readings.

Common Causes of Fault Code 19

Several factors can lead to the gas cartridge temperature exceeding or falling below the acceptable range:

  • Environmental Extremes: The most common cause is the device being exposed to ambient temperatures that are too hot or too cold for its specified operating conditions. This could happen if the device is installed outdoors without proper environmental protection or in areas susceptible to extreme weather fluctuations.
  • Improper Placement:
    • Direct Sunlight: Installing the device in direct sunlight can cause its internal temperature to rise significantly, especially on hot days.
    • Proximity to Heat Sources: Placing the E3Point too close to furnaces, heating vents, industrial machinery, or other heat-generating equipment can lead to overheating.
    • Proximity to Cold Sources: Conversely, placement near cold storage units, air conditioning vents, or in unheated areas during winter can cause temperatures to drop excessively.
  • Insufficient Ventilation: Lack of proper airflow around the device can trap heat, preventing natural cooling, or allow cold air to pool, leading to temperature extremes within the enclosure.
  • Internal Component Issues: While less common for this specific fault, a malfunctioning internal component or sensor could potentially contribute to incorrect temperature readings, though the fault primarily indicates an actual temperature excursion.

Implications of a Temperature Fault

When fault code 19 is active, the E3Point device may not be able to accurately detect gas levels, potentially leading to false alarms or, more critically, failure to detect real gas hazards. Sustained exposure to out-of-range temperatures can also reduce the lifespan of the gas cartridge and other internal components.

Troubleshooting and Resolution Steps

Addressing fault code 19 typically involves identifying and mitigating the source of the temperature extreme. Here are practical steps to resolve the issue:

  1. Check Ambient Temperature:

    • Use an external thermometer to measure the temperature of the environment immediately surrounding the E3Point device.
    • Compare this reading to the specified -4°F to 122°F operating range.
  2. Optimize Device Placement:

    • Relocation: If the device is in direct sunlight, near heat/cold sources, or in an area with extreme temperatures, consider relocating it to a more stable environment.
    • Shading/Insulation: For outdoor installations, provide appropriate shading to protect from sun exposure, or use insulated enclosures to shield against extreme cold.
  3. Ensure Proper Ventilation:

    • Clear any obstructions (e.g., dust, debris, other equipment) that might be blocking airflow around the device.
    • Ensure there is adequate space around the E3Point for proper heat dissipation.
  4. Allow for Acclimation:

    • If the device was recently moved from a different temperature environment, allow it some time to naturally acclimate to the new conditions before re-evaluating the fault.
  5. Professional Inspection:

    • If the fault code persists despite verifying and correcting environmental conditions, it may indicate a deeper internal issue with the gas cartridge or the device's temperature sensor. In such cases, it is advisable to contact a qualified technician or Honeywell support for further diagnosis and service.

Summary of Fault Code 19

Below is a quick reference for Honeywell Fault Code 19:

Fault Code Description Trigger Condition Affected Devices Recommended Action
19 Temperature Fault Gas cartridge temperature outside the range of -4°F to 122°F Honeywell E3Point Adjust environmental conditions, optimize device placement, ensure ventilation.

By understanding the cause and implementing these troubleshooting steps, users can effectively resolve Honeywell fault code 19 and ensure the continued accuracy and reliability of their gas detection systems.