How to Calculate Superheat Chart?

Published in Refrigeration Diagnostics 4 mins read

Calculating superheat involves determining the temperature difference between the refrigerant's actual exit temperature from the evaporator (T2) and its saturated evaporating temperature (T1), with refrigerant charts serving as crucial tools to obtain the saturated temperature value. While there isn't a direct "superheat calculation chart" in the typical sense, various industry-standard charts are indispensable for gathering the necessary data to perform this critical calculation.

Understanding Superheat Calculation

Superheat is a fundamental measurement in refrigeration and air conditioning systems, indicating how much warmer the refrigerant vapor is than its boiling point (saturation temperature) at a given pressure. It's a key indicator of system efficiency and proper refrigerant charge.

As per industry standards, you can calculate superheat by taking the difference between the actual exit temperature of the refrigerant from the evaporator (T2) and the saturated evaporating temperature (T1). This process ensures that all liquid refrigerant has fully vaporized before entering the compressor, protecting the compressor from damage due to liquid slugging and optimizing system performance.

The Superheat Formula

The calculation for superheat is straightforward:

Superheat = T2 - T1

Where:

  • T2 = The actual temperature of the refrigerant vapor as it exits the evaporator coil. This is measured using a temperature probe attached to the refrigerant line.
  • T1 = The saturated evaporating temperature of the refrigerant. This temperature corresponds to the pressure of the refrigerant inside the evaporator, where it is boiling from a liquid to a vapor.

Step-by-Step Calculation of Superheat

To accurately calculate superheat, follow these steps:

  1. Measure Actual Evaporator Exit Temperature (T2): Attach an accurate temperature clamp or probe to the refrigerant suction line (the larger insulated line) as close as possible to the evaporator's outlet. Record this temperature.
  2. Measure Evaporator Suction Pressure: Connect a pressure gauge to the suction service port on the compressor or suction line. Record the pressure reading (usually in PSI or kPa).
  3. Determine Saturated Evaporating Temperature (T1) using a Refrigerant Chart: This is where the "chart" aspect becomes crucial. For the specific type of refrigerant in the system (e.g., R-410A, R-22, R-134a), consult a pressure-temperature (P-T) chart. Locate the measured suction pressure on the chart and find the corresponding saturated temperature for that refrigerant. This value is T1.
  4. Calculate Superheat: Subtract T1 from T2. The result is the superheat value.

The Role of Charts in Superheat Determination

While you don't "calculate a chart," refrigerant charts are indispensable tools for obtaining the saturated evaporating temperature (T1), which is a crucial component of the superheat calculation.

Pressure-Temperature (P-T) Charts

Pressure-Temperature charts, also known as Saturation Charts, are essential for HVAC/R technicians. These charts list refrigerants and their corresponding saturated temperatures at various pressures. Every refrigerant has a unique P-T relationship.

Refrigerant Pressure (PSIG) @ 40°F Pressure (PSIG) @ 20°F
R-410A 118 90
R-22 68.5 43
R-134a 35 21

Note: Pressures are approximate and can vary slightly based on specific chart sources.

Pressure-Enthalpy (P-H) Diagrams

Pressure-Enthalpy (P-H) diagrams are more comprehensive thermodynamic charts used to visualize an entire refrigeration cycle. While not directly used for a simple superheat calculation formula, they graphically represent the superheated vapor region, allowing technicians to see the state of the refrigerant and understand how superheat affects the cycle's overall performance. They are valuable for in-depth analysis and troubleshooting.

Importance of Accurate Superheat Measurement

Measuring superheat accurately is vital for:

  • Preventing Liquid Slugging: Ensures all refrigerant has vaporized, preventing liquid from returning to the compressor, which can cause severe mechanical damage.
  • Optimizing Efficiency: Proper superheat levels ensure the evaporator coil is fully utilized for heat absorption, maximizing system efficiency.
  • Diagnosing System Issues: Abnormal superheat readings can indicate problems like an overcharge, undercharge, restricted flow, or faulty metering devices.
  • Protecting the Compressor: Maintains proper compressor cooling and lubrication by ensuring only superheated vapor enters the compressor inlet.

Practical Example of Superheat Calculation

Let's walk through an example:

  1. System: An air conditioning unit using R-410A refrigerant.
  2. Measured Evaporator Exit Temperature (T2): You measure the suction line temperature at the evaporator outlet and find it to be 50°F.
  3. Measured Evaporator Suction Pressure: You measure the suction pressure and find it to be 118 PSIG.
  4. Determine Saturated Evaporating Temperature (T1): You consult an R-410A Pressure-Temperature chart. For R-410A at 118 PSIG, the corresponding saturated temperature (T1) is 40°F.
  5. Calculate Superheat:
    Superheat = T2 - T1
    Superheat = 50°F - 40°F
    Superheat = 10°F

This 10°F superheat indicates that the refrigerant vapor leaving the evaporator is 10°F warmer than its saturated boiling temperature at that pressure, which is often within a desirable range for many systems.

In summary, while there isn't a "superheat chart" for calculation, the calculation itself is simple subtraction, and various refrigerant charts are absolutely essential tools for acquiring one of the two critical values needed for that calculation.